The recommended MINIMUM number of conduits connecting two located on the same floor is:

  1. One; 75 mm (trade size 3)
  2. Two; 75 mm (trade size 3)
  3. One; 100 mm (trade size 4)
  4. Two; 100 mm (trade size 4)

Answer(s): A



You are working on the design of a new, large ER/TR that will contain many racks and data cabinets including a large UPS system. Your recommendation to the architect for room access from inside the building is:

  1. Two 0.9 m (3 ft) solid doors
  2. One 1.5 m (5 ft) metallic roll top door
  3. One 1.2 m (4 ft) solid core, steel sheath door
  4. One 1.83 m (6 ft) solid core dual direction sliding door with removable sides
  5. One double door with a removable center post

Answer(s): E



At a minimum, convenience receptacles in an ER or TR are to be located ________ AFF.

  1. 150 mm (6 in)
  2. 300 mm (12 in)
  3. 375 mm (15 in)
  4. 450 mm (18 in)

Answer(s): A



On a survey of one of your client's buildings, you discover that one of the TRs, housing a considerable quantity of switching equipment, is at 25 degrees C (77 degrees F) with a relative humidity of 59 percent. This is considered to be:

  1. Within the normal range of temperature and humidity
  2. High temperature and normal humidity
  3. Normal temperature and high humidity
  4. High temperature and high humidity

Answer(s): C



The MINIMUM recommended lighting requirement in a telecommunications room (TR) at the point of cable terminations is:

  1. 150 lux
  2. 300 lux
  3. 500 lux
  4. 750 lux
  5. 1000 lux

Answer(s): C