Certain systems must exist relative to bonding and grounding at every site.
Which of the following is NOT one such system?

  1. AC grounding electrode system (e.g., in some countries it may also be known as the earthing system)
  2. Telecommunications bonding infrastructure
  3. Lightning protection system
  4. Equipment grounding system (e.g., in some countries it may also be known as the equipment bonding system)

Answer(s): C



As a guide, the recommended maximum AC current value on any bonding conductor should be less than ________ amperes.

  1. 0.50
  2. 1
  3. 5
  4. 10
  5. 20

Answer(s): B



You are designing a telecommunications grounding system for a telecommunications room (TR). The TMGB is located 15 m (50 ft) from the telecommunications rack.
What is the MINIMUM AWG of the ground conductor required?

  1. Two
  2. Three
  3. Four
  4. Six
  5. Eight

Answer(s): D



The impedance of the equipment grounding conductor can only be accurately measured with an instrument known as a(n):

  1. Volt ohm meter
  2. Power distribution unit
  3. Exothermic weld connection
  4. Ground impedance tester
  5. Amp calculator

Answer(s): D



Based on documentation contained within the Insulated Cable Engineers Association (ICEA) standard P32-382, Short Circuit Characteristics of Insulated Cable, a copper conductor is capable of safely carrying one ampere for ________ second(s) for every 42.25 circular mils.

  1. One
  2. Five
  3. Twelve
  4. Twenty
  5. Thirty

Answer(s): B