A telecommunications outlet/connector may be provided using all listed below EXCEPT:

  1. Wireless AP connectivity
  2. Balanced twisted-pair outlets
  3. Optical fiber connectors
  4. 4p4c (4 position, 4 contact) connector

Answer(s): D



Important considerations when designing telecommunications distribution within modular furniture include all of the following EXCEPT:

  1. How the furniture pathways will be connected to horizontal building pathways
  2. Separation of telecommunications cabling and electrical power
  3. Diameter of cable to be installed
  4. Maximum initial fill ratio of 40 percent when derated because of corners

Answer(s): D



In a run requiring 15 m (50 ft) of cable between the floor distributor and the consolidation point, the MAXIMUM length of cable allowed between the CP and the telecommunications outlet is:

  1. 27.4 m (90 ft)
  2. 36.5 m (120 ft)
  3. 45.8 m (150 ft)
  4. 75 m (242 ft)
  5. 90 m (295 ft)

Answer(s): D



When specifying telecommunications outlet boxes, all of the following should be considered EXCEPT:

  1. Outlet box shall be a minimum of 100 mm (4 in) x 100 mm (4 in) x 76 mm (3 in)
  2. Outlet boxes should be installed near an electric outlet at the same height
  3. Different outlet boxes have different support requirements
  4. Floor mounted telecom outlet boxes should be coordinated with furniture to minimize the potential trip hazard
  5. Outlet boxes must be of adequate size so that minimum cable bend radius requirements are not exceeded

Answer(s): A