For TRs that contain active equipment, what is the minimum temperature and humidity range requirements?

  1. 50 to 95 degrees F and between 30 to 55 percent relative humidity.
  2. 64 to 75 degrees F and below 85 percent relative humidity.
  3. 50 to 95 degrees F and below 85 percent relative humidity.
  4. 64 to 75 degrees F and between 30 to 55 percent relative humidity.

Answer(s): D



Multiple TRs on the same floor should have a least one trade size 3 conduit ran between them.

  1. True
  2. False

Answer(s): A



The minimum door size should be which of the following?

  1. 2.0 ft wide and 6 ft tall.
  2. 4 ft wide and 7 ft tall.
  3. 6 ft wide and 8 ft tall.
  4. 3.0 ft wide and 6.7 ft tall.

Answer(s): D



The color brown, of the cross-connect field color code, identifies which of the following?

  1. Network connections.
  2. First-level backbone.
  3. Interbuilding backbone
  4. First-level backbone.

Answer(s): C



A TR may contain the demarcation point for one or more service providers or an interbuilding entrance facility.

  1. True
  2. False

Answer(s): A