When turning on the maintenance bypass switch of UPS5000-E after the maintenance completed, to make sure loads continue to be powered, which of the following should be noted?

  1. The bypass module has no alarm, and input is normal.
  2. Even if the bypass module is abnormal, the maintenance bypass switch can be turn off.
  3. If the UPS is in EPO status, the maintenance bypass switch can be turned off
  4. The battery input is normal

Answer(s): A



The compressor discharge temperature of NetCol5000-A is high, the possible reasons ( ).

  1. The refrigerant loop or component is blocked.
  2. The outdoor unit is not properly installed.
  3. The condenser is dirty or blocked.
  4. The refrigerant is insufficient

Answer(s): A,B,C



When four UPS2000-G-20K parallel setting is "3+1", the capacity of the system is ( ) KVA.

  1. 80
  2. 40
  3. 60
  4. 100

Answer(s): C



The cold/hot aisle containment systems can improve cooling efficiency and reduce power consumption.

  1. TRUE
  2. FALSE

Answer(s): A