What differentiated features does the FusionModule800 have over competing products? () (Multiple Choice)

  1. Rack-mounted frequency-converting air conditioner
  2. Integrated design of cooling and power
  3. Light-load dehumidification of air conditioning
  4. iBattery

Answer(s): A,B,C,D



The battery voltage of the UPS2000-G is 240 V for the 6-10 kVA capacity models, and is 480 V for the 15 kVA and 20 kVA capacity models.

  1. TRUE
  2. FALSE

Answer(s): A



The battery capacity is calculated on actual power when the actual load power is used for UPS configuration.

  1. TRUE
  2. FALSE

Answer(s): A



The number of batteries can be adjusted in the process of UPS configuration.

  1. TRUE
  2. FALSE

Answer(s): A



If the total current of a battery string is 1000 A and three battery strings are configured, the most economic cable configuration between the UPS and the main switch box is ():

  1. 120 mm2 (382 A) x 3
  2. 150 mm2 (441 A) x 3
  3. 185 mm2 (506 A) x 3
  4. 240 mm2 (599 A) x 3

Answer(s): B