Free H19-311 Exam Braindumps
Huawei Certified Pre-sales Associate- Data Center Facility Questions 101–105 (page: 22)

Updated On: 10-Feb-2026

The UPS5000-A features the design of reliability, high efficiency, and simplicity. Which of the following statements are correct about the UPS5000-A-400/500K? (Multiple Choice)

  1. The UPS5000-A-400/500K has built-in components for parallel operation.
  2. The UPS5000-A-4O0/500K supports the upflow mode.
  3. The UFS5000-A has two control units.
  4. The input voltage of the UPS ranges 138-485 V AC.

Answer(s): A,C,D



Assuming that the discharge power specified in a battery specification is 400W@1.67V@15min, if the system load requirement is 1400 W, () battery strings shall be configured.

  1. 3
  2. 4
  3. 5

Answer(s): B



For the UPS2000-G series (6 kVA to 20 kVA), the main input voltage ranges from 80 V to 280 V, and the input frequency ranges from 40 Hz to 70 Hz. A wide input range effectively reduces the battery switch times, failure probability, and battery charge/discharge times, helping improve the battery life.

  1. TRUE
  2. FALSE

Answer(s): A



Considering that the UPS is fully configured but has a low system load rate in the initial stage, the UPS5000-E is designed with a smart hibernation function, which can improve system load rate to ensure highly efficient operation. In case of smart hibernation, how many redundant power modules does the UPS5000-E have at least?

  1. 0
  2. 1
  3. 2

Answer(s): B



The external maintenance bypass of the UPS typically adopts ()-pole circuit breakers.

  1. 1
  2. 2
  3. 3
  4. 4

Answer(s): D



Viewing page 22 of 46
Viewing questions 106 - 110 out of 225 questions