Huawei Certified Pre-sales Associate- Data Center Facility Questions 106–110 (page: 23)

Updated On: 10-Feb-2026

Which of the following parallel system does the UPS5000-A support? (Multiple Choice)

  1. N+X parallel system
  2. Dual-bus system
  3. Parallel system not supported

Answer(s): A,B



With parallel configuration, the UPS2000-G supports the use of a single () card for multiple UPSs in parallel. (Multiple Choice)

  1. SNMP
  2. Modbus
  3. Dry contact
  4. Parallel

Answer(s): A,B



If the system is configured with 15-minute battery backup duration, the discharge cutoff voltage of a single battery is ().

  1. 1.60 V
  2. 1.67 V
  3. 1.75 V
  4. 1.80 V

Answer(s): B



The maximum capacity of a single-racked UPS5000-E (50 kVA power module) is 300 kVA.

  1. TRUE
  2. FALSE

Answer(s): A



Which of the following statements are correct about the UPS5000-A smart feature? (Multiple Choice)

  1. It supports NetEco monitoring software and centralized UPS monitoring.
  2. It supports smart battery management, which can efficiently extend the battery service life.
  3. The NetEco monitoring software of the UPS5000-A supports SMS or email remote alarm reporting.

Answer(s): A,B,C