Free Huawei H19-371_V1.0 Exam Questions (page: 25)

Using UPS5000-E (50kVA power module), the actual load is 160kW, the rack 1+1 redundancy, the single-machine backup power scheme is adopted, each rack has 3 groups of batteries, each group is 40, and the capacity of the main switch box is ( )

  1. 250A
  2. 320A
  3. 500A
  4. 630A

Answer(s): C



How many 12V batteries can the optional battery inspection instrument of UPS5000-A-400/500K support? ( )

  1. 12
  2. 24
  3. 32
    D .40.

Answer(s): B



The wrong description about the reliability of NetCol5000-C row-level air conditioner is: ().

  1. It adopts dual power supply, and the two power supply adopts automatic switching mode
  2. Large-scale data centers such as operators and large corporate headquarters are more popular with such air conditioners. .
  3. More application of SMEs Netcp15000-A air conditioner multi-fan air supply: online maintenance is possible.
  4. Cannot be used in scenarios without raised floor, because condensate drainage cannot be connected to the pipe

Answer(s): D



The total current of the battery pack is 1000A, and 3 sets of batteries are configured. The most economical configuration of the cable from the UPS to the main switch box is ( )

  1. 120mm 2 (382A) X3
  2. 150mm 2 (441A) X3
  3. 185mm 2 (506A) X3
  4. 240mm 2 (599A) X3

Answer(s): B