Huawei H12-425 Exam Questions
HCIP-Data Center Facility Deployment V1.0 (Page 6 )

Updated On: 21-Feb-2026

Which statement are correct about UPS5000-E.

  1. It is modular UPS
  2. The input voltage range is 138-485V
  3. The input frequency range is 40-70Hz.
  4. A maximum of two UPS can be connected in parallel

Answer(s): A,B,C



During Nitrogen injecting, a pressure relief valve must be installed on the nitrogen cylinder.

  1. TRUE
  2. FALSE

Answer(s): A



If multiple data centers need to be monitored at the same time hierarchical deployment is available.

  1. TRUE
  2. FALSE

Answer(s): A



Site selection is one challenge for the traditional data center

  1. TRUE
  2. FALSE

Answer(s): A



UPS2000-G-20 kVA displays that the batteries status NA, the possible reason is (___________________).

  1. Batteries are not connected.
  2. Batteries are undervoltage
  3. Batteries are connected properly
  4. The neutral wire of the batteries is not connected

Answer(s): A